Display and control panel AMS 348i SSI
42
AMS 348
i
SSI
Leuze electronic GmbH + Co. KG
LSR
Warning - laser prefailure message:
Laser diode old, device still functional, exchange or have repaired.
TMP
Warning - temperature monitoring:
Internal device temperature above/below permissible range.
PLB
Plausibility error:
Implausible measurement value. Possible causes: light beam interruption, outside
of measurement range, permissible internal device temperature considerably
exceeded or traverse rate >10m/s.
Depending on the configuration, either zero or the last valid measurement value is
output at the interfaces.
ATT
Warning - received signal:
Laser exit window or reflector soiled or fogged by rain, water vapor or fog. Clean or
dry surfaces.
ERR
Internal hardware error:
The device must be sent in for inspection.
Bar graph
Indicates the strength of the received laser light.
The center bar represents the ATT warning threshold. The distance value remains
valid and is output at the interfaces.
If no bar graph is available, the PLB status information appears at the same time.
The measurement value is assessed as implausible. Depending on the configuration,
either zero or the last valid measurement value is output at the interfaces.
Interface info
"LNK0" and "LNK1" in the display indicate an existing Ethernet connection for BUS IN and
BUS OUT. If the status info "LNK0" or "LNK1" is not displayed although the data line is
connected, the connection is faulty. The abbreviation "SSI" stands for an activated SSI inter
-
face.
The connection status is additionally signaled by a green/orange multicolor LED below the
BUS IN and BUS OUT connector, see chapter "LINK LED for BUS IN and BUS OUT".
Display of existing
Ethernet connection
Position value
IO1 LSR PLB
LNK0
IO2 TMP ATT
LNK1
ERR
SSI
+ 87.000m
Activated SSI interface indicator