Commissioning
Test commissioning
Test commissioning with terminal control
7
91
EDS84ABD302 EN 4.0
4. Enable controller:
Set terminal X4/RFR to HIGH-Potential (reference: X4/GND).
5. Vary the motor speed or the motor velocity with the potentiometer or by defining
different fixed setpoints:
DI2
DI1
Motor speed
0
0
Setpoint by potentiometer
0
1
40 % of C00011 (reference speed)
1
0
60 % of C00011 (reference speed)
1
1
80 % of C00011 (reference speed)
Internal Keypad
Code
Subcode
Motor speed
-2-
_
`
C...
C051
xxxx
C00051
-
Observe
z
the actual speed value:
C00051
z
appearing messages
92
6. Save the settings with mains failure protection by entering the value ”1” in code
C002, subcode 7.