Electrical installation
Devices in the power range from 0.37 to 3 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
70
EDS84ABD302 EN 4.0
Motor connection
Terminal X105
Labelling
Description
U, V, W
Motor
PE
PE conductor
84BDGG012
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
E84AVBxE3714
1 ... 2.5
18 ... 12
0.5
4.5
3.5 x 0.6
E84AVBxE5514
E84AVBxE7514
E84AVBxE1124
E84AVBxE1524
E84AVBxE2224
E84AVBxE3024
Connection of external brake resistor
X109
84BLDGG020
Fig. 6-14
Inserting terminal X109
Before plugging in the terminal X109:
1. Switch off the controller and wait for at least 3 minutes before start working.
2. Make sure that there is no residual voltage.
3. Pull the cover carefully to the side without removing it completely.
4. Plug in the terminal.