Electrical installation
Installation according to EMC (installation of a CE-typical drive system)
Shielding
6
50
EDS84ABD302 EN 4.0
6.2
Installation according to EMC (installation of a CE-typical drive system)
Design of the cables
ƒ
It is imperative to comply with the regulations concerning minimum cross-sections
of PE conductors. The cross-section of the PE conductor must be at least as large as
the cross-section of the power connections.
ƒ
The cables used must comply with the approvals required for the location (e.g. UL).
6.2.1
Shielding
Requirements
ƒ
The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or
nickel-plated copper braid.
– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ
Motor
ƒ
Motor holding brake (shielding is required when being integrated into the motor
cable; connection to optional motor brake control)
ƒ
Motor temperature monitoring
ƒ
Analog signals (inputs and outputs; single-sided shield connection to the controller)
The following connections need not be shielded:
ƒ
12-V supply
ƒ
Digital signals up to a cable length of 3 m
Connection system
ƒ
Connect the shield with a large surface and fix it with a conductive clamp.
ƒ
Connect the shield directly to the terminal X13.
– If required, additionally connect the shield to the conductive and earthed
mounting plate in the control cabinet.
– If required, additionally connect the shield to the cable clamp rail.