Technical data
Rated data
Operation at rated mains voltage 230 V
4
28
EDS84ABD302 EN 4.0
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c
d
L1, N - laying system
e
L1, N
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVBxx2512
C6
6
1.5
-
-
10
14
≥
30
E84AVBxx3712
C6
6
1.5
-
-
10
14
E84AVBxx5512
C10
10
1.5
-
-
10
14
E84AVBxx7512
C10
10
1.5
-
-
10
14
E84AVBxx1122
C16
16
1.5
-
-
15
14
E84AVBxx1522
C20
20
2.5
-
-
20
12
E84AVBxx2222
C25
25
4
4)
-
-
25
10
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4).
The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable
cross-sections are not permissible for technical reasons.
2)
Use UL-approved cable, fuses, and fuse holders only.
UL fuse: voltage
≥
240 V, tripping characteristic ”H”, ”K5” or ”CC”.
The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature
< 45°C. Smaller cable cross-sections are not permissible for technical reasons.
3)
Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
4)
only with pin-end connector
c
Circuit breaker
d
Fuse
e
Fuse
Observe national and regional regulations