Electrical installation
Devices in the power range from 0.37 to 3 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
67
EDS84ABD302 EN 4.0
6.4.2
Terminal assignment of the power connections
Strip cables
X105
84BLMOTL001_a
U, V, W
PE
b
c
e
a
d
[mm]
[mm]
E84AVBxE3714
95
150
7
180
7
E84AVBxE5514
E84AVBxE7514
E84AVBxE1124
E84AVBxE1524
E84AVBxE2224
E84AVBxE3024
How to proceed:
1. Strip motor cable as specified.
2. Fold back shield of motor cable over the cable sheath. Keep unshielded cable ends as
short as possible.
3. Fix shield on the cable sheath (e.g. using a heat-shrinkable tube).
4. Fasten wire end ferrule to PE cable.
– The other cables may be wired without using wire end ferrules.
5. Connect motor cable shield to PE terminal of inverter.
– For strain relief of the cables, additional measures are required.