Electrical installation
Control terminals
External supply voltage 24 V
6
77
EDS84ABD302 EN 4.0
6.5.4
External supply voltage 24 V
X4
DC 24 V
(+15.0 ... +30.0 V)
12I GND
DI2
50
mA
DI1
DI3
DI4
RFR
X4
3.3k
3.3k
3.3k
3.3k
3.3k
12
V
24E
DO1
GND
GND
E84AVBx...
8400BLGG004
8400BLD046
Fig. 6-19
Connection to an external supply voltage
Terminal X4
Labelling
Description
GND
A1U
AR
12I
RFR
DI1
DI2
DI3
DI4
24E
DO1
24E
Connection for an external 24 V supply by a safely separated
power supply unit (SELV/PELV), IEC 61131-2
(required for mains-independent supply of the control electronics)
12I
Output 12 V, max. 50 mA
for connecting digital inputs via potential-free contacts
GND
Ground reference potential for the digital inputs and outputs
84BLGGX005
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
flexible
0.2 ... 1.5
24 ... 16
0.5
4.5
3.5 x 0.6
with wire end ferrule