Electrical installation
Devices in the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)
Terminal assignment of the power connections
6
62
EDS84ABD302 EN 4.0
Mains connection
Terminal X100
Labelling
Description
L1
Mains phase L
L2/N
Mains phase L/Neutral conductor N
PE
PE conductor on the supply side
84BDGG001
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
E84AVBxE2512
E84AVBxE3712
E84AVBxE5512
E84AVBxE7512
E84AVBxE1122
1 ... 2.5
18 ... 14
0.5
4.5
3.5 x 0.6
E84AVBxE1522
1 ... 2.5
18 ... 12
1 ... 4
18 ... 10
E84AVBxE2222
1 ... 4
18 ... 12
1 ... 6
18 ... 10
For inverter drives of type E84AVBDE
2222
and E84AVBDE
1522
, the following should be
considered:
ƒ
when the inverter is connected to the mains without a mains choke, the terminal
X100 can accommodate
– cables with cross-sections of maximum 4 mm
2
without wire end ferrules.
– cables with cross-sections of maximum 4 mm
2
or thicker with a wire end ferrule
only if pin-end connectors are used.