Commissioning
Messages
7
92
EDS84ABD302 EN 4.0
7.6
Messages
The current status of the controller can be checked via:
ƒ
six LEDs in different colours (
83)
ƒ
messages as follows:
Message
Status
Meaning
PASS
Password input
CAL
blinking
Identification is in progress.
CAL
/
StoP
alternatively blinking
Identification is ready to start. Operation is not enabled yet.
CAL
/
Err
alternatively blinking
Identification is not ready to start. Either C00088, or C00089, or
C00090 is 0.
bF
blinking
Identification error. Drive ID stored in EPM does not match the drive
ID stored in the controller.
CL
constant
Current limit set by C00022 is reached
FCL
constant
Fast current limit value (higher than value of C00022) is reached
FSt
constant
Flying restart function is in progress
dEC
constant
Deceleration is temporarily suspended because of higher bus
voltage
br
flashes during the hold
time of the DC brake
DC brake is in progress