© Copyright Lenovo 2015
Chapter 3: Installing G8264CS Hardware and Options
49
Statement 26
CAUTION:
Do not place any object on top of rack-mounted devices.
To install the 1U air-duct option in a 19” rack, complete the following steps.
1. Loosen and remove the mounting screws from both sides of the mounting rail
and set them aside to reuse for securing the foam carrier in the next step.
2. Place the half shears on the rear side of the foam carriers and use the M3.5
mounting rail screws to secure the foam carrier assemblies snugly against the
rear of the G8264CS unit. Torque the screws to approximately 1.1 Nm ± 0.1 Nm
(10 inch-pounds).
Note:
There are additional M3.5 screws in the air-duct assembly kit.
Half shear
Foam carrier snug against rear of unit
Reuse mounting screws
Mounting screws
Содержание RackSwitch G8264CS
Страница 1: ...Lenovo RackSwitch G8264CS Installation Guide ...
Страница 10: ...10 G8264CS Installation Guide ...
Страница 14: ...14 G8264CS Installation Guide ...
Страница 18: ...18 G8264CS Installation Guide ...
Страница 32: ...32 G8264CS Installation Guide ...
Страница 58: ...58 G8264CS Installation Guide ...
Страница 78: ...78 G8264CS Installation Guide ...
Страница 92: ...92 G8264CS Installation Guide ...
Страница 96: ...96 G8264CS Installation Guide ...