6) FUNCTIONS OF DIP SWITCH S1
Select the functions by means of dip-switch S1 of the control unit or by means of the indicator light of the digital selector
(consult sect. 9.2 for the settings of digital selector).
Selector / Control unit
DIP 1 ON = Push & Go activated. Door opened in the manual mode.
OFF = Push & Go inhibited.
DIP 2 ON = Wind stop activated. Prevents the door from opening accidentally in a draught
OFF = Wind stop inhibited.
DIP 3 ON = cyclic function activated (repeated door aopening and closing).
OFF = cyclic function inhibited.
DIP 4 ON = electro-lock output activated (see sect.8 for a description of pontentiometers TM9 & TM10 wich allow
operation with the electro-lock to be optimized).
OFF = electro-lock output inhibited.
DIP 5 ON = OPENING BY MOTOR, CLOSING BY SPRING AND MOTOR.
This function is recommended for doors that may be subjected to wind force when closing and
for all those situations in which the force of the spring alone may not be sufficient to guarantee that the
door fully closes.
OFF = OPENING BY MOTOR, CLOSING ONLY BY SPRING.
DIP 6 ON = activated the initial set-up cycle (see sect.4);
allows power limitation to be indicated by the buzzer.
OFF= inhibits the buzzer warning for power limitation.
DIP 7 ON = door open condition with function selector in the “||” position.
OFF= night lock condition with function selector in the “||” position.
DIP 8 ON = courtesy function for the disabled. See section 10 for a description of operation.
OFF= courtesy function inhibited
DIP 9 ON = if the operation program NIGHT LOCK is selected, the door opens and remains open 10” before closing
again.
OFF= if the operation program NIGHT LOCK is selected, the door does not open.
In NIGHT LOCK, the door can only be opened with the EMERGENCY input, or with the SPYCO radio
control.
DIP 10 ON = automatically increases the pause time if the door cannot close on account of the high flow of persons
OFF = constant pause time.
DIP 11 (can only be selected with digital selector)
ON = work program selected by means of digital selector (see sect. 9).
OFF =work program selected by means of the function selector switch (see sect. 5.1) or the
manual selector (see sect. 5.2).
DIP 12 (can only be selected with digital selector)
ON = enables regulation of the functions (dip-switch S1) and potentiometers (from TM1 to TM5) by means of digital selector.
OFF = enables regulation of the functions (dip-switch S1) and potentiometers (from TM1 to TM5) by means of control unit
LGN.
All the adjustments to dipswitch S2, potentiometers TM6, TM7, TM8, TM9, TM10 and to the TECHNICAL MENU are
made by meas of digital selector alone.
WARNING!! : This DIP switch must be set prior to the INITIAL SETUP described in chapter 4.