FUNCTION TABLE
1: Function to be set in the menu "Initial Set-up" of the digital selector before door start
*: Default setting of the function
FUNCTION
STATE
EXPLANATION
F01
1
OFF
Selection of the work program selector: digital selector ET‑DSEL or T‑NFC.
ON
Choice of the work program selector: EV‑MSEL mechanical selector
F02
OFF*
Standard function: the electric lock activates when the door is closed only in the Night Lock work program.
ON
Bank function: the electric lock activates when the door is closed in all work programs
F03
1
OFF
Electric lock type selection: FAIL SECURE «EV‑EBSFSE» or BISTABLE «EV‑EBSBIS»
ON
Electric lock type selection: FAIL SAFE «EV‑EBSFSA»
F04
1
OFF
Electric lock for pharmacy function not installed
ON
Double electric lock for pharmacy function: active (see par. "PHARMACY FUNCTION")
F05
OFF*
Electric lock inactive when the door is closed in the EXIT ONLY work program
ON
Electric lock active when the door is closed in the EXIT ONLY work program
F06
1
OFF
Battery module NOT present
ON
Battery module ET‑BAT1 / ET‑BAT2 present.
F07
OFF*
Operation with battery: in the absence of mains power supply, the door continues to operate normally
ON
Operation with battery: in the absence of mains power supply, the door opens and remains open in the automatic work programs
F08
OFF*
Battery monitoring: if the battery is low or damaged, the control unit buzzer beeps before opening for 10 cycles
ON
Battery monitoring: if the battery is low or damaged, the door opens and stays open in automatic programs
F09
OFF*
Operation without mains power supply with battery low: the door operates normally
ON
Operation without mains power supply with battery low: the door opens and stays open
F10
OFF*
In the night lock program, in the event of mains power supply outage, the control unit remains powered with the battery until its draining
ON
In the night lock program and with door closed, in case of failure of mains power supply outage, the automation switches into stand‑by mode to reduce to a
minimum the use of battery. To restart the automation from stand‑by, give a pulse control on the Wake input (terminals 28‑29). See paragraph "SWITCHING
TO STAND BY MODE".
F11
1
OFF
Automation model: ETERNA 150 / 300T (telescopic)
ON
Automation model: ETERNA 150
F12
1
OFF
E.C.1 closing safety sensor input inactive; when the safety sensor is not installed on the E.C.1 input
ON
E.C.1 closing safety sensor input active; closing safety sensor on E.C.1 input installed
F13
1
OFF
E.C.2 closing safety sensor input inactive; when the safety sensor is not installed on the E.C.2 input
ON
E.C.2 closing safety sensor input active; closing safety sensor on E.C.2 input installed
F14
1
OFF
E.O.1 opening safety sensor input inactive; when the safety sensor is not installed on the E.O.1 input
ON
E.O.1 opening safety sensor input active; opening safety sensor on E.O.1 input installed
F15
1
OFF
E.O.2 opening safety sensor input inactive; when the safety sensor is not installed on the E.O.2 input
ON
E.O.2 opening safety sensor input active; opening safety sensor on E.O.2 input installed
F16
1
Function active if
F12 or F13 = ON
OFF
Tests on closing safety sensors E.C.1 and E.C.2 inactive; for sensors which are not pre‑arranged for the monitoring
ON
Test on closing safety sensors E.C.1 and E.C.2 active; for sensors pre‑arranged for automatic door monitoring by the automation (cat.2/pl.c). For details,
please refer to the paragraph "Safety sensors".
F17
1
Function active if
F14 or F15 = ON
OFF
Tests on opening safety sensors E.O.1 and E.O.2 inactive; for sensors which are not pre‑arranged for the monitoring
ON
Test on opening safety sensors E.O.1 and E.O.2 active; for sensors pre‑arranged for automatic door monitoring by the automation (cat.2/pl.c). For details, refer
to the paragraph “Safety sensors”.
F18
1
Function active if
F16 or F17 = ON
OFF
Safety sensors test with LOW logic level. Function active if F16 or F17 = ON
For details, refer to the paragraph “Safety sensors”.
ON
Safety sensors test with HIGH logic level. Function active if F16 or F17 = ON
For details, refer to the paragraph “Safety sensors”.
F19
OFF*
The tripping of the safety sensor while opening E.O.1 / E.O.2 is effective for the entire opening run
ON
The activation of the safety sensor while opening E.O.1 / E.O.2 is effective only in the last 500mm of the opening run
F20
OFF*
The activation of the safety sensor during opening E.O.1 / E.O.2 slows down the leaf opening motion until the end of the run is reached.
ON
The activation of the safety sensor during opening E.O.1 / E.O.2 stops leaf motion until the obstacle is removed.
F21
OFF*
PRJ38 FT1/FR1 photocell: inactive
ON
PRJ38 FT1/FR1 photocell: active
F22
Function active if
F21 = ON
OFF*
PRJ38 FT1/FR1 photocell working as a stop sensor in the panic exit breakout system
ON
PRJ38 FT1/FR1 photocell working as safety photocell for closing.
Warning!
This feature does not provide safety during closing as required by the standard EN16005.
The use of the photocell PRJ38 is acceptable only if in addition to the safety sensors monitored in accordance with the standard EN12978.