22
Mascot LX Service Manual
Many of the most serious trouble conditions on this unit will cause a “lockout,” and
the controller will present a lockout code on the display. Often the lockout code will
take you directly to the cause of the problem. After you have corrected the prob-
lem, press the Reset button to exit from the lockout.
Fig. A2-1 Example of Lockout Screen
E001 – Memory error lockout
There has been a lockout due to a problem with the EEPROM memory in the con-
trol unit.
• Press the Reset button to try to cancel the lockout.
• Power down the unit, wait two minutes, then power on the unit again.
• If this does not restore normal operation, replace the SIT control board. See
E002 – Fan speed error
There has been a lockout because the fan did not reach normal speed.
• Check for a blockage in the vent.
• Check the wiring to the blower. Disconnect the signal connection to the blower
- the blower should run at full speed. See Section B11. If the blower reaches
full speed, the blower itself is probably OK.
• If the blower does not reach full speed, remove the blower and check for free
movement of the fan. Replace the blower if necessary.
• If the blower moves freely, replace the SIT control board. See Section B30.
A2
Lockout Codes