27
Mascot LX Service Manual
“Notification” codes indicate unusual conditions that do not cause the unit to lock
-
out. Some of these codes can be useful during troubleshooting.
Fig. A3-1 Example of Notification Screen
N01 - Fan speed limited due to flue gradient not detected.
The flue sensor includes two sensor elements. The controller looks for the same
reading from both. If the sensor readings are different, beyond a pre-set limit, the
controller will present this Notification code. The boiler will continue to run at Low
Fire. If this condition continues, the controller will present a Lockout message.
• Once the problem has been corrected, press Reset to remove the limitation.
N02 - Fan speed limited due to high temperature at outlet
This refers to a high water temperature at the water outlet.. The controller watches
this input. If the sensor reading reaches a pre-set limit, the controller will present
this Notification code. The boiler will continue to run at Low Fire. If this condition
continues, the controller will present a Lockout message.
• Once the problem has been corrected, press Reset to remove the limitation.
N03 - Fan speed limited due to excessive delta T
This refers to a large difference between the water inlet and outlet temperatures.
The controller watches these inputs. If the difference between the sensor readings
reaches a pre-set limit, the controller will present this Notification code. The boiler
will continue to run at Low Fire. If this condition continues, the controller will pres
-
ent a Lockout message.
• Once the problem has been corrected, press Reset to remove the limitation.
N04 - Fan speed limited due to high flue temperature
This refers to a high exhaust temperature in the flue.. The controller watches this
input. If the sensor reading reaches a pre-set limit, the controller will present this
Notification code. The boiler will continue to run at Low Fire. If this condition con
-
tinues, the controller will present a Lockout message.
• Once the problem has been corrected, press Reset to remove the limitation.
Notification Codes
A3
Содержание MASCOT LX
Страница 2: ......
Страница 6: ...Mascot LX Service Manual iv...
Страница 24: ...Mascot LX Service Manual 18...
Страница 38: ...32 Mascot LX Service Manual...
Страница 76: ...70 Mascot LX Service Manual...
Страница 90: ...84 Mascot LX Service Manual Appendix 3 Wiring Diagrams continued App3 cont Fig App3 2 120V Wiring Diagram...
Страница 93: ......