Appendix 1 - SIT Parameter Codes (continued)
App1
cont.
Parameter
Description
Default
P58
Frost protection start pump temperature
45°F
P59
Frost protection start burner temperature
37°F
P60
Frost protection stop burner hysteresis
5°F
P61
Low outdoor air temperature for heat curve (LOD)
25°F
P62
High setpoint for test curve (HBT)
180°F
P63
High outdoor air temperature for heat curve (HOD)
70°F
P64
Low setpoint for heat curve (LBT)
120°F
P65
Outside temperature disabling central heat demand
(WWSD)
90°F
P66
Outside temperature disabling central heat hysteresis
5°F
P67
TH1 shift heat curve
0°F
P68
Boost function time
0 sec.
P69
Boost function temperature step per period
0°F
P70
Minimum user setting central heat setpoint
32°F
P71
Maximum user setting central heat setpoint
190°F
P72
Block offset central heat demand
10°F
P73
Block hysteresis central heat demand
20°F