Operating Displays
Operating Mode Displays -
When the unit is operating normally, use the Up and Down buttons to rotate through the
following functions:
• Outlet temperature - The setpoint for central heat is adjustable. Range 45°F - 189°F,
default 130°F
* Inlet temperature
• Delta T (the difference between the outlet and inlet temperatures)
• Outdoor sensor (if the outdoor temperature sensor is installed
• Flue temperature
• Domestic hot water temperature (if this is a Combi model or is connected to an external
tank). The setpoint is adjustable. Range 68°F - 189°F, default 120°F
• System temperature (if a System probe is installed). The setpoint is adjustable. Range
45°F - 189°F, default 130°F.
• Burner rate (if the burner is lit)
You can also use the Up and Down buttons to step through these displays. The following
images show how to interpret these displays.
Operating Modes -
The control system uses four modes:
Operating Mode - While the unit is running, the controller will rotate between several stan-
dard displays.
User Mode -
This mode allows the user to change some of the setpoints. To go to
User Mode, press and hold the OK/Select button for one second.
Installer Mode -
This allows the installer to change all of the parameters used to install
and configure the boiler. To go to the Installer Mode, press and hold
the OK/Select and Down buttons for five seconds. For details, see the
Appendix.
Service Mode -
This mode should only be used by technicians who have been trained
in service procedures on the Mascot LX. For details, see Section C -
Содержание MASCOT LX
Страница 2: ......
Страница 6: ...Mascot LX Service Manual iv...
Страница 24: ...Mascot LX Service Manual 18...
Страница 38: ...32 Mascot LX Service Manual...
Страница 76: ...70 Mascot LX Service Manual...
Страница 90: ...84 Mascot LX Service Manual Appendix 3 Wiring Diagrams continued App3 cont Fig App3 2 120V Wiring Diagram...
Страница 93: ......