Mascot LX Service Manual
A1
Quick Checkout Procedure (continued)
Continued next page
Yes
No
Incoming gas
pressure is
OK?
Adjust regulator.
Check with gas
company
Disconnect the Central Heat or System sensor
and insert a jumper to create a
permanent “Call For Heat.”
(terminals 5 and 6 on the low voltage terminal strip)
Yes
No
Does the
Central Heat or
System symbol
light up?
Replace the SIT controller board.
The unit should try to fire.
The smallest segment in the flame
display should blink.
Yes
No
Boiler
fires?
Check the direct spark
ignition. See Section B16.
Does the
pump start?
See Section B17 - “Pump Problems.”
Yes
No