4.2.1 Set up and connection of the external sensor.
For controlling the heating according to the external temperature, it is necessary to install the external
temperature sensor.
CAUTION
The sensor must be set up in a shady spot.
The sensor must not be set up above a window or door.
It must be located
away from heat sources.
For measuring external temperature, the sensor type
PT 1000
is used.
Temperature sensor for external temperature.
The direction of connecting cables.
T
Temperature sensor for external temperature.
CAUTION
The external sensor must be connected and watertight to prevent water penetration.
4.2.2 Minimal clearance from the device
The air direction and minimal clearances of the external device from walls for seamless operation,
maintenance and servicing.
m
in
.
3
0
0
m
m
min. 1500 mm
min. 300 mm
m
in
.
2
0
0
0
m
m