4.5 Removal of the external device cover
See chapter 4.2.4.
4.6 Connecting the external unit
In the scope of the external unit it is necessary to connect the following two cables (see technical data
7.2):
External unit power cable.
Plated communication cable between external and internal control unit.
4.6.1 Power cable connection of the external unit
DANGER
Connecting the device to the power source can only be performed by a qualified installer in
a voltage-free state.
CAUTION
The cable must be routed through the cord anchorage installed before the connecting
terminals in the indoor unit. Make sure the cable connected in the indoor unit is relieved from
strain.
CAUTION
Wrong dimensioning of the power cable or too weak terminal fuses of the device could lead
to an overload of the safety elements on the power grid of the building which could lead to
overheating of the electrical installation. Follow the requirements listed in this manual.
CAUTION
The communication cable must not be laid together with energy cables (in accordance with
good engineering practise and regulations).
Connecting clips of the supply cable WPLV-09-S1 NT
The device is powered by the supply cable ~230 V / 50 Hz and is connected to connecting clips L / N /
PE ( ). The dimensions of the power cables are listed in the technical information (chapter 7.2).
The clip L1 (brown, grey, black wire) / the clip N blue wire) / the clip PE ( ) (yellow-green wire)