4.2 Location of the device
CAUTION
The concrete pedestal must carry the weight of the device. See technical
information.
The device must be levelled
NOTE
It is obligatory to consider the minimal clearance from obstacles for ensuring unobstructed
access for maintenance and service of the device.
NOTE
The location of the device has to be accessible with manual transport devices to ensure
undisturbed delivery of replacement parts and equipment for maintenance and servicing.
Costs connected with hiring special equipment for installing the device, servicing and
maintenance are charged the operator separately and are not subject of the warranty.
The device must not be set up at a location, which is subject to stronger and lengthy gusts of wind (i.e.
bora wind); they could obstruct the normal air circulation through the evaporator which could result in
disruptions in operation.
In case the device is installed in the wind direction, it is necessary to install adequate wind protection.
Wind protection must be robust enough to prevent the influence of the wind. The best option is
a concrete or brick version.
The height and width of the wind protection must be at least 150 % of the basic dimensions of
the device. Only these dimensions enable adequate wind protection of the device.
The wind protection must be located at least 3000 mm away from the external device to ensure
sufficient air flow.
NOTE
The device must be set up in a leeward location.
NOTE
Salt or dust gathering on the outer heat conductor must be regularly cleaned (dust once
yearly and salt in coastal regions at least three times yearly) or rinsed with water.