©Termo-tehnika, d.o.o.
36
ID.: 17-16-24-3006-03 | 12.2016
Device
WPLV-09-S1 NT
WPLV-14-S1 NT
Dimensions and mass – transpot
Dimensions (W x H x D)
mm
1150 x 956 x 740
1150 x 1502 x 470
Mass
kg
89
142
Dimensions and mass – net
Dimensions (W x H x D)
mm
990 x 834 x 400
990 x 1380 x 400
Mass
kg
77
126
Noise
Level of sound power
dB (A)
63
67
Level of sound pressure at a distance of
1 m
dB (A)
55
59
Level of sound pressure at a distance of
5 m
dB (A)
41
45
Level of sound pressure at a distance of
10 m
dB (A)
35
39
Communication
Connection between ext. and inter. unit
Plated cable 3 x 0.75 mm
2
/ 2x2x0,6 mm
2
(LiYCY)
Connection to BMS
MODBUS protocol (UTP cable – connection RJ45) – RS 485
Connection to the internet
8)
UTP 5e cable - connection RJ45 - Ethernet
Miscellaneous
Protection class
External unit
IPX4
1)
/
2)
COP (Coefficient of Performance) is a card for performance efficiency of the device, the heating number which is a
quantity without unit. Computer-wise COP is the ratio between the energy gained - heat (in cooling it is heat taken
away) and electrical energy needed for the functioning of the device.
3)
EER (Energy Efficiency Ratio) is an abbreviation for the coefficient of the cooling energy efficiency. Mathematically
EER is the ratio between the effective cooling power and effective electrical power in [kW].
4)
With the cable we have taken into account laying B2 from the table A.52.4 – IEC 60364-5-52. The cable in the
installation pipe is fixed to the wall. The dimensions of the electrical cables must always be checked or determined by
the designing engineer of electrical installations.
4*)
/
5)
/
6)
/
7)
/
8)
Connection to the internet is not necessary for the operation of the device but it is necessary for remote control through
the Home Cloud service. It is also advisable for faster troubleshooting of the device’s operation.
9)
For internal HM devices, see technical data for HM.
10)
/
11)
/
12)
Circuit breaker with “slow” characteristics for devices with very high inrush current.