CN3 CONNECTOR AND USABLE CABLES:
To connect, simply push the cable or the ferrule directly onto the corresponding hole.
To disconnect the cables, press lightly on the respective orange plate.
Solid cable section min (mm²) 0.2
Solid cable section max (mm²) 0.5
Section of braided cable min (mm²) 0.2
Section of braided cable max (mm²) 0.5
Flexible cable section with min ferrule without sheath (mm²) 0.25
Flexible cable section with max ferrule without sheath (mm²) 0.75
Flexible cable section with min ferrule with sheath (mm²) 0.25
Flexible cable section with max ferrule with sheath (mm²) 0.5
INPUT:
All inputs (Pin from 1 to 20) of the CN3 connector are and they required a 24V DC positive signal.
The signals can be provided either by using an external source (in this case the negative of the
source with the negative common of the KDU unit must be shared) or by using the pin 21 (24VDC)
in the CN3 connector (in this case just make a contact with opto-isolator, relay or button to activate
the desired input).
Example on how to enable Input signals by using an external source