Configuration and Installation
The
DNX R-2F/FC
modules can be used in both the “Passive” and “Active” modes of
operation. The installation of the
i
NS should be executed in order of presentation.
C
onfiguration steps:
1)
Configure the local communication settings for each DNX R-2F/FC.
The communication settings are configured for the respective fire alarm panel by
setting the Rotary switch 1 in Table 11.
2)
Configure the Module as Master or
Slave (ONLY required for ACTIVE
Mode)
When using the DNX R-2F/FC modules in active mode, a master is required for
commissioning the network and managing the fault recovery procedure.
It is important that there is only a single (ONE) DNX R-2F/FC master per class A
ring or class B radial.
Adjust the Master/Slave selection on the device by setting or re-setting DIP
SWITCH 1 of set 6 as per selection in Table 10.
Master Module
Slave Module
Set 6
Set 6
3)
Selecting ACTIVE or PASSIVE Mode of operation local to a module
Setting the Mode local to the Module:
You can set the Mode of operation of the module by setting or re-setting DIP
SWITCH 4 of set 6 as per selection in Table 10.
Active Mode (DNA)
Passive Mode (DNP)
Set 6
Set 6
22
Man-1492
DNX-R-2F/FC-K
Содержание DNX-R-2F-K
Страница 36: ...Figure 18b Passive Mode Settings and Dual Port CIE with Hybrid Connections 36 Man 1492 DNX R 2F FC K...
Страница 38: ...Figure 20 iNS LED Indication 38 Man 1492 DNX R 2F FC K...
Страница 39: ...Figure 20a iNS LED Indication 39 Man 1492 DNX R 2F FC K...
Страница 40: ...Notes 40 Man 1492 DNX R 2F FC K...
Страница 41: ...41 Man 1492 DNX R 2F FC K...
Страница 42: ...42 Man 1492 DNX R 2F FC K...