Locations of Interface ports, LEDs and DIP-switches
LED Indicators
LED
Status
Colour
Description
Q &S LED C1/
Q &S LED B1
(Q&S Debug
disabled)
ON
Amber
Signal amplitude (on RS-485) and quality LED 1 indicates that the
signal quality is greater than 20%
Signal amplitude and quality is POOR.
OFF
The signal quality is less than 20%
Q &S LED C2/
Q &S LED B2
(Q&S Debug
disabled)
ON
Green
Signal amplitude (on RS-485) and quality LED 2 indicates that the
signal quality is greater than 50%
Signal amplitude (on RS-485) and quality is ACCEPTABLE.
OFF
The signal quality is less than 50%
Q &S LED C3/
Q &S LED B3
(Q&S Debug
disabled)
ON
Green
Signal amplitude (on RS-485) and quality LED 3 indicates that the
signal quality is greater than 90%
Signal amplitude (on RS-485) and quality is GOOD.
OFF
The signal quality is less than 90%
Port B TX
ON
Green
A good data packet has been transmitted out of port B
OFF
No valid data has been transmitted out of port B
Port B RX
ON
Green
A good data packet has been received on port B
OFF
No valid data has been received on port B
TERM B
Port B side of
Link established
ON
Green
In mode 2: Port B has successfully established and validated
healthy communication across the link to a remote port C terminal.
OFF
In mode 2: Port B has failed to successfully establish and validate
healthy communication across the link to a remote port C terminal.
Port C TX
ON
Green
A good data packet has been transmitted out of port C
OFF
No valid data has been transmitted out of port C
Port C RX
ON
Green
A good data packet has been received on port C
OFF
No valid data has been received on port C
TERM C
Port C side of
Link established
ON
Green
In mode 2: Port C has successfully established and validated
healthy communication across the link to a remote port B terminal.
OFF
In mode 2: Port C has failed to successfully establish and validate
healthy communication across the link to a remote port B terminal.
Port A TX
ON
Green
A good data packet has been transmitted out of port A1 or A2
OFF
No valid data has been transmitted out of port A1 or A2
Port A RX
ON
Green
A good data packet has been received on port A1 or A2
OFF
No valid data has been received on port A1 or A2
Status port B
ON
Green
The link connected to port B is HEALTHY with data activity.
Amber
There is a FAULT present on the link connected to port B.
OFF
There is NO fault on port B, but INSUFFICIENT DATA activity.
FLASH
Amber
There is a signal QUALITY FAULT present on the link connected
to port B.
Green
Port B is in a state of establishing the link
Status port C
ON
Green
The link connected to port C is HEALTHY with data activity.
12
Man-1492
DNX-R-2F/FC-K
Содержание DNX-R-2F-K
Страница 36: ...Figure 18b Passive Mode Settings and Dual Port CIE with Hybrid Connections 36 Man 1492 DNX R 2F FC K...
Страница 38: ...Figure 20 iNS LED Indication 38 Man 1492 DNX R 2F FC K...
Страница 39: ...Figure 20a iNS LED Indication 39 Man 1492 DNX R 2F FC K...
Страница 40: ...Notes 40 Man 1492 DNX R 2F FC K...
Страница 41: ...41 Man 1492 DNX R 2F FC K...
Страница 42: ...42 Man 1492 DNX R 2F FC K...