Description (*DNA R-2F/FC Mode Only) 

Switch Set 6  

Master selection (Only used in Active Mode) 

Slave selection (Only used in Active Mode) 

Commissioning Mode Enabled (Only used in Active Mode) 

Commissioning Mode Disabled (Only used in Active Mode) 

Class B - (Stops the Fault LED for indicating a fault with an open point in the bus) 

Class A 

Active Mode selection  

Passive Mode selection 

Table 10 

16

Man-1492 

DNX-R-2F/FC-K 

Содержание DNX-R-2F-K

Страница 1: ...Man 1492 Intelligent Network Solutions DNX R 2F FC K Hybrid RS485 and Full Optic Fibre Intelligent Network Analyser User Manual Man 1492 DNX R 2F FC K Rev 02...

Страница 2: ...are made in relation to the accuracy and reliability or contents of this document Kentec reserves the right to revise this document or withdraw it at any time without prior notice Under no circumstanc...

Страница 3: ...supply Care recommendations Follow the care recommendations below to maintain full operation of the unit and to fulfil the warranty obligations This unit must not be operated with the cover removed Do...

Страница 4: ...dard Industrial Environments EN 61000 6 4 Emission Standard Industrial Environments Safety EN 60950 IT Equipment Table 1 Ratings Power 18 to 36V 24V DC nominal 170mA at 24V Temperature Operating 10 to...

Страница 5: ...Panel IN Port 9 In Out line RS 485 ARCNET PORT A1 Panel IN Port 10 In Out line RS 485 ARCNET PORT A1 Panel IN Port 11 Screen Shield RS 485 ARCNET PORT A2 Panel OUT Port 12 In Out line RS 485 ARCNET P...

Страница 6: ...a network analysis tool The mode can be selected through Set 6 switch 4 in Figure 6 and Table 10 Note The DNX R 2F FC will operate in a basic mode unless upgraded to unlock the additional features off...

Страница 7: ...ngle optic fibre interface and an RS 485 interface FC or CF In hybrid mode FC CF the optic fibre interface on the DNX R 2F FC can be configured as either port B or C by selecting the correct rotary sw...

Страница 8: ...on to port A1 and or A2 is via an RS 485 or ARCNET interface The connection to ports A1 A2 B and C are as indicated in Figures 18a and 18b depending on the mode of operation The different operational...

Страница 9: ...DNX R 2F FC Class A Redundant Hybrid Network Figure 4d ACTIVE or PASSIVE Mode DNX R 2F FC Class B Radial Hybrid Network Note The Class A or B mode of operation is applicable to both ACTIVE and PASSIV...

Страница 10: ...s and protects the data bus through monitoring the data it routes The modules are transparent to the CIE protocols only routing and analysing the data structure but not the content The maximum standar...

Страница 11: ...witch 2 RS 485 Failsafe setting Failsafe biasing 820 Protection Installation Fault Tolerant up to 44 V Table 6 Optic Fibre Port B C Electrical specification LC Type Optic Fibre connectors Data rate 10...

Страница 12: ...OFF In mode 2 Port B has failed to successfully establish and validate healthy communication across the link to a remote port C terminal Port C TX ON Green A good data packet has been transmitted out...

Страница 13: ...hy FLASH Port B Optic Fibre SFP transceiver Warning or Alarm Indication ON Green ADC Active OFF ADC disabled FLASH Unused IO PORT LED 2 ON Amber Port A has been internally disconnected signal OVERDRIV...

Страница 14: ...Third party Data flow monitoring across the network Table 9a Supported Feature Set SFP signing All of the supplied SFP transceivers are signed to mark calibration with the DNX R 2F FC product and any...

Страница 15: ...SW 1 and DIP Switch Set 6 refer to Figure 6 both of which are externally accessible You should therefore not need to open the product enclosure The settings as presented in Tables 10 and 11 After chan...

Страница 16: ...on Only used in Active Mode Commissioning Mode Enabled Only used in Active Mode Commissioning Mode Disabled Only used in Active Mode Class B Stops the Fault LED for indicating a fault with an open poi...

Страница 17: ...ns shown in Table 11 Figure 7 Rotary selector Rot Switch Setting Position Function Panel 0 Port B Fibre Port C Fibre Taktis 1 Port B RS 485 Port C Fibre Taktis 2 Port B Fibre Port C RS 485 Taktis 3 Po...

Страница 18: ...7 Not Used X 8 Not Used X 9 Not Used X A Not Used X B Not Used X C Not Used X D Not Used X E Not Used X F Not Used X Table 11 18 Man 1492 DNX R 2F FC K...

Страница 19: ...irtual serial communication port with the specific com port address confirmed using the Windows Control Panel Refer to the User Manual for the IVIEW Software application tool for installation details...

Страница 20: ...ormance of each link is monitored to track and record its associated Quality of Service QoS The cable performance for the data rate of transmitted signal will vary according to the type and length of...

Страница 21: ...corded to track transmission path performance drift The information is retained for system degradation monitoring in support of life safety preventative maintenance programs Digital Optical Monitoring...

Страница 22: ...R 2F FC modules in active mode a master is required for commissioning the network and managing the fault recovery procedure It is important that there is only a single ONE DNX R 2F FC master per class...

Страница 23: ...ptic link when the modules have been powered up The Link establishing procedure will take approximately 2 to 3 seconds to complete with the Link established LED in an ON state once the process has bee...

Страница 24: ...as per DIP SWITCH 1 of set 6 the commissioning mode switch is used to force the DNX R 2F FC module to manage the commissioning mode by auto allocating addresses broadcasting operational details and p...

Страница 25: ...ation is stable Note Clock Synchronization The Master DNX R 2F FC will resynchronize all of the DNX R 2F FC slave module clocks with its own clock after each recovery cycle This is done to ensure timi...

Страница 26: ...s B radial link by setting or resetting Switch 3 of Set 6 as indicated in the table below Note This external switch selection of Class A or B is ONLY available from Micro Firmware version 9 8X onwards...

Страница 27: ...3 and BS5839 1 This topology is illustrated in Figure 11 Figure 11 Class A Hybrid Network Class B Non redundant radial configuration The DNX R 2F FC module also supports the class B non redundancy opt...

Страница 28: ...nsceivers The BiDi transceivers use two frequencies for Tx and Rx on each fibre to carry the Tx and Rx signals on a single fibre This application is useful for the following converting a radial system...

Страница 29: ...he metallic conductor cable needs to be earthed on one of the two sides to provide a path to ground any coupled signal interference With both sides grounded an unwanted path for circulating currents i...

Страница 30: ...lecting the correct SFP transceiver for the cable to which it is connected Transceiver types supported Multi mode MM Single Mode SM Bi directional BiDi Figure 15 Connections of Mixed Optic Fibre Types...

Страница 31: ...a CIE is selected using DIP SWITCH 2 of set 4 as per an Advanced User Guide The DNX R 2F FC L supports two external protocols at various baud rates The performance of the network is however dependent...

Страница 32: ...ed in Figure 17a This feature supports the tracking of CIE watchdog events if the auxiliary PSU being monitored is disconnected during the watchdog event Figure 17a Example of a configuration for moni...

Страница 33: ...he optic fibre interfaces Earth terminal The earth terminal provides a surge path for transients on the Port A circuit Relay terminal The relay may be used to trigger an external alarm under fault con...

Страница 34: ...ice can be found in the following application notes Type Title Document Number Application Note Network Redundancy with DNA R 1 DNA R 2 502 DNARIE01 A 01 Application Note Multi fault tolerant networks...

Страница 35: ...lustrates the wiring connections for the DNX R 2F FC modules Note The port connections must have Port B connected to Port C as reflected in the diagram Figure 18a Passive Mode Settings and Dual Port C...

Страница 36: ...Figure 18b Passive Mode Settings and Dual Port CIE with Hybrid Connections 36 Man 1492 DNX R 2F FC K...

Страница 37: ...d in Figure 19 Figure 19a INS010 Multimode transceiver Figure 19b INS011 Single mode transceiver Figure 19c INS012 Single mode Bi directional transceiver To pair with the INS013 Figure 19d INS013 Sing...

Страница 38: ...Figure 20 iNS LED Indication 38 Man 1492 DNX R 2F FC K...

Страница 39: ...Figure 20a iNS LED Indication 39 Man 1492 DNX R 2F FC K...

Страница 40: ...Notes 40 Man 1492 DNX R 2F FC K...

Страница 41: ...41 Man 1492 DNX R 2F FC K...

Страница 42: ...42 Man 1492 DNX R 2F FC K...

Отзывы: