MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
87
7. Flow sensor position: Inlet or outlet flow (A code)
The installation position of the flow sensor can be adjusted in the SETUP loop. This means that the calculator can be
changed from being an outlet meter to being an inlet meter and vice versa. A symbol in the top left corner of the
calculator’s display shows whether the calculator is configured as an inlet or outlet meter.
8. Energy unit (B code)
The calculator’s measuring unit (B code) and resolution (CCC code) can be adjusted in the SETUP loop. It is thus
possible to change if the calculator’s energy readings should be displayed in kWh MWh, GJ or Gcal.
Note: The resolution of the energy unit will always follow the one specified for the CCC code that a given MULTICAL®
803 is configured with. See the CCC tables in paragraph 3.3.3. Note that if you select kWh for a MULTICAL® 803
calculator with a CCC code where kWh is not possible, MULTICAL® 803 automatically switches to MWh.
9. Primary address of module slot 1
The primary address of module slot 1 in MULTICAL® 803 can be adjusted in the SETUP loop. The address can be
selected in the interval 0…250.
10. Primary address of module slot 2
The primary address of module slot 2 in MULTICAL® 803 can be adjusted in the SETUP loop. The address can be
selected in the interval 0…250.
11. Primary address of module slot 3
The primary address of module slot 3 in MULTICAL® 803 can be adjusted in the SETUP loop. The address can be
selected in the interval 0…250.