MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
39
EE=19 Time-controlled tariff
The time-controlled tariff is used for time division of heat consumption. If TL2 = 08:00, TL3 = 16:00 and TL4=23:00,
the daily consumption from 08:00 until 15:59 is accumulated in TA2, whereas the consumption during the evening
from 16:00 until 22:59 is accumulated in TA3 and the consumption during the night from 23:00 until 07:59 is
accumulated in TA4.
TL2 must include fewer hours than TL3 and TL3 must include fewer hours than TL4.
From and incl. TL2 to TL3 Accumulation in TA2 and main register
TL3 must follow TL2
TL4 must follow TL3
From and incl. TL3 to TL4 Accumulation in TA3 and main register
From and incl. TL4 to TL2 Accumulation in TA4 and main register
The time-controlled tariff is suitable for billing in housing areas close to industrial areas with large district heating
consumption as well as for billing industrial customers.
EE=20 Heat/cooling volume tariff
The heat/cooling volume tariff is used to divide volume into heat and cooling consumption in combined heat/cooling
meters, i.e. the tariff divides the consumed volume into heat and cooling volume for combined heat/cooling meters.
The total volume is accumulated in the register V1, whereas TA2 accumulates the volume consumed together with
E1 (heat energy) and TA3 accumulates the volume consumed together with E3 (cooling energy).
EE=20 only functions in heat/cooling meters of the meter types 3 and 6.
(TA4 is not used in this tariff type).
t1
>
t2 and t1
≥
θ
hc
Volume is accumulated in TA2 and V1
(heat energy)
TL2 and TL3 are not used
t1
>
t2 and t1
≤
θ
hc
Volume is accumulated in V1 only
t2
>
t1 and t1
≤
θ
hc
Volume is accumulated in TA3 and V1
(cooling energy)
t2
>
t1 and t1
≥
θ
hc
Volume is accumulated in V1 only
t1 = t2 and t1
≥
θ
hc
Volume is accumulated in V1 only, no
counting in energy registers
t1 = t2 and t1
≤
θ
hc
Volume is accumulated in V1 only, no
counting in energy registers
EE=21 PQ tariff
The PQ tariff is a combined power and flow tariff. TA2 functions as power tariff and TA3 functions as flow tariff.
P
≤
TL2 and Q
≤
TL3 Accumulation in main register only
TL2 = power limit (P)
TL3 = flow limit (Q)
P
>
TL2
Accumulation in TA2 and main register
Q
>
TL3
Accumulation in TA3 and main register
P
>
TL2 and Q
>
TL3
Accumulation in TA2, TA3 and main
register
The PQ tariff can, for example, be used for customers who pay a fixed charge based on max power and max flow (TL4
and TA4 are not used in this tariff type).