MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
131
Information code
Description
Remedy
Display duration of 5 s
Communication error
on input V1 as well as
incorrect meter factor
on input V2.
Separate the calculator and check that ULTRAFLOW® X4 is correctly
mounted in the connection terminals of input V1. Check that the
ULTRA FLOW® X4 flow sensors are identical. Then repeat the
procedure in paragraph 8.1.1.1 from step ③.
Display duration of 5 s
Incorrect meter factor
on input V1 and
communication error
on input V2.
The config logger is full. It is no longer possible to replace
ULTRAFLOW® X4 on either input V1 or input V2 by a different size
than the recently logged size for input V1. Separate the calculator
and check that ULTRAFLOW® X4 is correctly mounted in the
connection terminals of input V2. Check that the ULTRA FLOW® X4
flow sensors are identical. Then repeat the procedure in paragraph
8.1.1.1 from step ③.
Display duration of 5 s
Incorrect meter factor
on both input V1 and
input V2.
The config logger is full. It is no longer possible to replace
ULTRAFLOW® X4 on either input V1 or input V2 by a different size
than the recently logged size for input V1.
8.1.2
Need for longer cables between MULTICAL® 803 and ULTRAFLOW®
In general, cables of up to 10 m can be used between MULTICAL® and ULTRAFLOW®. In case a longer cable is
required, Kamstrup can deliver two solutions: Cable Extender Box (6699-036) or Pulse Transmitter (6699-903). With
these solutions, the cable length can be extended with up to 30 m or 100 m, respectively. Both solutions have a
number of advantages and disadvantages that are outlined in the table below.
Application options
Cable Extender Box Pulse Transmitter
Up to 30 m cable between
ULTRAFLOW® and MULTICAL®
Yes
Yes
Up to 100 m cable between
ULTRAFLOW® and MULTICAL®
No
Yes
Info codes and data communication
between ULTRAFLOW® and
MULTICAL®
Yes
No
Galvanic separation between
ULTRAFLOW® and MULTICAL®
No
Yes
IP class
IP65
IP67
When Pulse Transmitter is used between ULTRAFLOW® and MULTICAL®, the calculator cannot establish data
communication with ULTRAFLOW® due to the galvanic separation. In order to avoid incorrect info codes, it is thus
necessary to deselect the info codes that are based on data communication between MULTICAL® and ULTRAFLOW®
(Info = 16-1024-2048-128-4096-8192-16384-32768).
The above info codes can be deselected by means of METERTOOL HCW, for example by changing from CCC code 4xx
to 1xx.