MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
23
3.4
Configuration number
The software configuration of MULTICAL® 803 is defined on the basis of the configuration number. Below you see an
overview of the calculator’s configuration number. Each part of the configuration number is described in more detail
in the following paragraphs.
A - B - C C C - DDD - EE - FF - GG - L - M - N - PP
- RR - T - VVVV
Flow sensor position
Inlet
3
Outlet
4
Measuring unit
GJ
2
kWh
3
MWh
4
Gcal
5
Auto Detect CCC codes (ULTRAFLOW®
Normal resolution (7 digits)
8 0 7
Normal resolution (8 digits)
8 0 8
High resolution (8 digits)
8 1 8
Static CCC codes
Reed switch (7 digits)
0 x x
Electronic, fast pulse (7 digits)
1 x x
Electronic, fast pulse (8 digits)
2 x x
Kamstrup, UF X4 (7 digits)
4 x x
Kamstrup, UF X4 (8 digits)
5 x x
Electronic, slow pulse (7 digits)
9 x x
Display
Heat meter
2xx
Heat/cooling meter
3xx
Cooling meter
5xx
Tariffs
No active tariff
00
Power tariff
11
Flow tariff
12
t1-t2 tariff
13
Inlet tariff
14
Outlet tariff
15
Time-controlled tariff
19
Heat/cooling volume tariff
20
PQ tariff
21
Pulse inputs A and B
See paragraph 3.4.7
FF
GG
Integration mode
Fixed mode (2 s)
Backlight by push button
4
Fixed mode (2 s)
Backlight always on
9
Leakage limits (V1/V2)
OFF
0
1.0 % of qp + 20 % of q
1
1.0 % of qp + 10 % of q
2
0.5 % of qp + 20 % of q
3
0.5 % of qp + 10 % of q
4
Leakage limit, Cold water (In-A, In-B)
OFF
0
30 minutes without pulses
1
One hour without pulses
2
Two hours without pulses
3
Pulse Transmitter/Divider
Out-C: V1/4
5 ms
73
Out-C: V1/1, Out-D: V2/1
3.9 ms
80
Out-C: V1/1
3.9 ms
82
Out-C: V1/4
22 ms
83
Pulse outputs for count registers
E1 and V1 or E3 and V1
10 ms
94
E1 and V1 or E3 and V1
32 ms
95
E1 and V1 or E3 and V1
100 ms (0.1 s)
96
Controlled output based on data commands
Controlled output
99