15.2.3
Changing the configuration of MULTICAL
®
302
To program new values into the meter it must be in Setup Loop. If the MULTICAL
®
302 has not yet been used it will be in
“Transport State” and the programming can take place without further action. METERTOOL HCW for MULTICAL
®
302 will
automatically set the meter to Setup Loop.
If the MULTICAL
®
302 has been in use prior to the programming, the meter will have to be set to “Setup loop” before
the programming can commence. This can be done only by first breaking the
SETUP seal and short-circuiting the
contact points behind the seal with short-circuit pen type 66-99-278. After that, “Setup” is displayed.
Note!
This should be done only by an authorized installer, and an approved seal has to be replaced after programming.
After shorting
SETUP seal, the meter will remain in Setup loop for 4 minutes. To extend this period the front button
can be pressed, which will extend the Setup loop time by another 4 minutes. This can be done multiple times.
Figure 7
It is not possible to change the series number, as this is a unique number which is allocated to the meter during
production.
15.2.4
Time / date (Basic/Advanced Mode)
In this menu the built-in clock in the meter can be read out and adjusted either manually or by setting the meter to the
clock of the PC where METERTOOL HCW is running. It is only possible to write to a meter in “Setup Loop”.
15.2.5
Communication on/off (Advanced Mode)
In this menu the M-Bus radio transmitter can be switched on or off. This is useful if the meter is being transported e.g.
by air.
15.2.6
Configuration log (Advanced Mode)
Displays how many times the meter configuration has been changed since the first configuration. The maximum
number of configuration changes is 25.