MULTICAL® 302
Kamstrup A/S · Technical Description · 5512-1334_F1_GB_12.2016
37
7.3
Application types
MULTICAL
302 operates with 4 different energy formulas, E1, E3, E8 and E9, which are all calculated parallel with
each integration no matter how the meter is configured. E8 and E9 are used as basis for calculation of average
temperatures in inlet and outlet pipes only, whereas E1 and E3 are used for heat and cooling measurement
respectively.
7.3.1
E1 and E3
Energy types E1 and E3 are described by application examples below.
302-Txxxxxx2xx
Application A
Closed heating system with one flow sensor
Heat energy: E1 = V1(T1-T2)k
T1:Inlet or T2:Outlet
Flow sensor V1 is placed in inlet or outlet as
selected during Config.
302-Txxxxxx5xx
Application B
Closed cooling system with one flow sensor
Cooling energy: E3 = V1 (T2-T1)k
T2:Inlet or T1:Outlet
Flow sensor V1 is placed in inlet or outlet as
selected during Config.
302-Txxxxxx3xx
302-Txxxxxx6xx
Application C
Closed heat/cooling system with one flow sensor
Heat energy: E1 = V1(T1-T2)k
T1:Inlet or T2:Outlet
Cooling energy: E3 = V1(T2-T1)k
T2:Inlet or T1:Outlet
Flow sensor V1 is placed in inlet or outlet as
selected during Config.