MULTICAL® 302
28
Kamstrup A/S · Technical Description · 5512-1334_F1_GB_12.2016
6.3
Straight inlet
MULTICAL
®
302 requires neither straight inlet nor straight outlet in order to fulfil the Measuring Instruments Directive
(MID) 2004/22/ EC and EN 1434:2007. A straight inlet section will only be necessary in case of heavy flow
disturbances before the meter. We recommend you to follow the guidelines of CEN CR 13582.
Optimal position can be obtained if you take the below-mentioned installation methods into consideration:
Figure 3
For general information concerning installation see CEN report
DS/CEN/CR 13582, Heat meter installation.
Instructions
in selection, installation and use of heat meters.
A
Recommended flow sensor position
B
Recommended flow sensor position
C
Unacceptable position due to risk of air
build-up
D
Acceptable position in closed systems
E
A flow sensor should not be placed
immediately after a valve, except for
block valves, which must be fully open
when not used for blocking
F
A flow sensor ought not be placed
directly before (suction side) or
directly after (outlet side) a pump
G
A flow sensor should not to be placed
close to a two-level double bend.