Operation
Sealing the pipework to the valve condensate tray
Proceed as follows when using the optional valve condensate tray to
catch condensation from the valves:
• Wall-mounted: Push the impermeable insulation from below through
the condensate opening on the pipe as far as the upper edge
(see Fig.
41)
.
• Glue the drip ring with insulation and the stem of the condensate
tray and press the rubber pipe cuffs onto the insulation
(see Fig. 42)
.
• Press the rubber pipe cuffs onto the insulation
(see fig. 43)
.
• If the insulation is not leak-proof and/or if the insulation is not
connected to the condensate tray and the drip ring, there is a danger
of condensate escaping and entering the room.
• Continue the insulation as far as the valves with ceiling units.
• When space is tight, e.g. with 4-pipe units (see Fig. 44), only continue
and stick the insulation as far as the valve condensate tray).
Fig. 41: Fix insulation through the
openings of the condensate tray
Fig. 42: Glue the insulation with
rubber pipe cuffs
Fig. 43: Press the rubber tube cuffs
onto the insulation
Fig. 44: Insulating with ceiling units
6.12 Sealing the Pipework to the Valve Condensate Tray (Accessory)
IMPORTANT NOTE!
Do not bend the valve condensate tray fitted at the
side .
Check the free condensate drain with water at latest
when commissioning the unit .