43
Venkon EC 115 V
43
Installation and Connection
Installing the Basic Unit
6.4.2 Ceiling Basic Unit
Allow for minimum clearances to any on-site resistance when
installing
(see Chapter 6.2).
Keyholes are provided at the top and bottom of the rear panel for
installation of the basic unit (Fig . 19) .
Mark drill holes (spacing of keyholes) on the ceiling as per Fig . 19 and
adjacent table and then drill holes .
Use suitable fixing material depending on the type of ceiling
mounting .
Fit fixing material into the ceiling.
Suspend basic unit on the 4 keyholes .
Level the unit for perfect operation. In the event of condensate, fit
the unit with a 1 .5% gradient towards the condensate discharge side .
Once the basic unit has been aligned, prevent the fixing material
from coming loose .
Provide for sound isolation between the fan coil
and the adjacent building if required.
Cam locks can be used on site for simple height
levelling.
Allow for minimum clearances to any on-site resistance when
installing
(see Chapter 6.2).
2 standing brackets are factory-fitted on the basic unit. Use suitable
fixing material to fix them and the basic unit to the floor. The 4 key
holes on the rear panel of the base unit are unused .
Mark drill holes (spacing of longitudinal holes) on the floor as per
Fig. 21
and adjacent table and then drill holes .
Use suitable fixing material depending on the floor covering.
Fit fixing material into the floor.
Align for correct and proper operation of the basic unit (note
condensate drain if necessary) .
Once the basic unit has been aligned, prevent the fixing material
from coming loose .
Provide for sound isolation between the fan coil
and the adjacent building if required.
6.4.3 Free-standing Basic Unit
Fig. 21: Dimensions for floor fixings
and connections
Mod
1
2
3
4
5
6
7
A
850 1000 1150 1300 1450 1600 2000
B
628 778
928 1078 1228 1378 1778