Venkon EC 115 V
20
20
Technical Data
Limits for tap water
3.6 Sound Values
3.7 Limits of the Medium (LPHW and CHW)
The sound levels change depending on the fan speed .
The sound pressure levels were calculated at an assumed room
insulation of 8 dB(A) . This corresponds to a distance of 2 m,
a room volume of 100 m³ and a reverberation time of 0 .5 s
(in accordance with VDI 2081) .
Only use water or a water-glycol mixture with up to 50%
glycol as the heating or cooling medium! Pay attention to the
suitability of the components on site, such as valves, boilers etc .
Use non-corrosive and non-flammable liquids as the heating
and cooling medium .
Media limits
Use water or water/glycol (max . 50%) as the medium . The
limits shown alongside for the medium apply to operation .
Mod 1 Mod 2 Mod 3 Mod 4 Mod 5 Mod 6 Mod 7
Sound pressure level L
P,A
[db(A)]
min .
<20
<20
20
20
20
<20
21
Max .
52
52
44
44
44
53
47
Sound power level L
W,A
[db(A)]
min .
24
24
26
26
26
27
29
Max .
60
60
52
52
52
61
55
Media limits
Parameter
Unit
Value
pH value (at 20 °C)
7,5 - 9
Conductivity (at 20 °C)
µS/cm
< 700
Oxygen content
mg/l
< 0,1
Total hardness
°dH
1 - 15
Dissolved sulphur
undetectable
Sodium
mg/l
< 100
Iron
mg/l
< 0,1
Manganese
mg/l
< 0,05
Ammonium content
mg/l
< 0,1
Chloride
mg/l
< 100
Sulphate
mg/l
< 50
Nitrite
mg/l
< 50
Nitrate
mg/l
< 50