Most sites distribute power through a main conduit that leads to frame-mounted power distribution
panels, one of which can be located at the top of the rack that houses the switch. An AC power cord
connects each power supply to the power distribution panel.
Each detachable AC power cord is 8 feet (approximately 2.5 meters) long. The coupler end of the
appliance cord inserts into the AC appliance inlet on the faceplate of the AC power supply. The coupler
type is C19 as described by the International Electrotechnical Commission (IEC) standard 60320. The
plug end of the power cord fits into the power source outlet that is standard for your geographical
location.
NOTE: In North America, AC power cords must not exceed 15 feet (approximately 4.5 meters) in
length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA 75, 5-2.2) and
210-52 and Canadian Electrical Code (CEC) Section 4-010(3). The cords shipped with the switch
to North America and Canada are in compliance.
QFX10000 AC, high-voltage alternating current (HVAC), and high-voltage direct current (HVDC) have
specific cord requirements. Use the following sections to determine the cable requirements based on the
model of your power supply and any mode settings:
• QFX10000-PWR-AC see
"QFX10000-PWR-AC Power Cable Specifications" on page 54
• JNP10K-PWR-AC2 with 20-A input, see
"JNP10K-PWR-AC2 Power Cable Specifications" on page
• JNP10K-PWR-AC2 with 30-A input, see
"JNP10K-PWR-AC2 Power Cable Specifications for 30-A
QFX10000-PWR-AC Power Cable Specifications
lists the AC power cord specifications for QFX10000-PWR-AC for various
countries and regions.
Table 17: AC Power Cord Specifications for QFX10000-PWR-AC Power Supplies
Country/Region
Electrical
Specifications
Plug Standards
Juniper Model
Number
Graphic
Argentina
250 VAC, 16 A,
50 Hz
IRAM Type RA/
3/20
CBL-EX-PWR-C19-
AR
54
Содержание QFX10016
Страница 1: ...QFX10016 Switch Hardware Guide Published 2022 09 09...
Страница 10: ...Compliance Statements for Environmental Requirements 428 x...
Страница 15: ...Figure 1 on page 5 shows a front and rear view of the QFX10016 4...
Страница 16: ...Figure 1 QFX10016 Front and Rear 5...
Страница 175: ...Installing the QFX10008 into a Rack Mounting a QFX10016 in a Four Post Rack Using a Mechanical Lift 207 164...
Страница 239: ...RELATED DOCUMENTATION QFX10008 Installation Overview QFX10002 System Overview 228...
Страница 266: ...CAUTION Do not bump the output connections If the connection hits a solid object it could damage the power supply 255...
Страница 270: ...1 ESD point Figure 113 ESD Point on QFX10016 Chassis Rear 1 ESD point 259...
Страница 287: ...Figure 130 Installing a JNP10K PWR AC2 in a QFX10016 276...
Страница 322: ...Figure 159 Installing a JNP10K PWR DC2 in QFX10016 311...
Страница 366: ...5 CHAPTER Troubleshooting Troubleshooting QFX10000 Modular Chassis 356...