b. Secure each negative (–) DC source power cable lug to the –48V (input) DC power input
terminal.
Figure 140: Connecting the QFX10000-PWR-DC Power Supply Cables to a QFX10000
Each power supply has two independent sets of DC power input terminals (INPUT 1: RTN –48V/–
60V: and INPUT 2: : RTN –48V/–60V). For feed redundancy, each power supply must be powered
by dedicated power feeds derived from feed INPUT 1 and feed INPUT 2. This configuration
provides the commonly deployed INPUT 1 / INPUT 2 feed redundancy for the switch. There is
basic insulation between the inputs and the chassis ground. Also, there is basic insulation between
RTN input feeds.
11. Install the plastic cable cover over each set of power cables by using the Phillips (+) screwdriver,
number 2, to tighten the screw.
290
Содержание QFX10016
Страница 1: ...QFX10016 Switch Hardware Guide Published 2022 09 09...
Страница 10: ...Compliance Statements for Environmental Requirements 428 x...
Страница 15: ...Figure 1 on page 5 shows a front and rear view of the QFX10016 4...
Страница 16: ...Figure 1 QFX10016 Front and Rear 5...
Страница 175: ...Installing the QFX10008 into a Rack Mounting a QFX10016 in a Four Post Rack Using a Mechanical Lift 207 164...
Страница 239: ...RELATED DOCUMENTATION QFX10008 Installation Overview QFX10002 System Overview 228...
Страница 266: ...CAUTION Do not bump the output connections If the connection hits a solid object it could damage the power supply 255...
Страница 270: ...1 ESD point Figure 113 ESD Point on QFX10016 Chassis Rear 1 ESD point 259...
Страница 287: ...Figure 130 Installing a JNP10K PWR AC2 in a QFX10016 276...
Страница 322: ...Figure 159 Installing a JNP10K PWR DC2 in QFX10016 311...
Страница 366: ...5 CHAPTER Troubleshooting Troubleshooting QFX10000 Modular Chassis 356...