JOHNSON CONTROLS
49
SECTION 6 - LON PROTONODE
FORM 450.50-N1
ISSUE DATE: 08/19/2019
6
PROTONODE LED FUNCTIONALITY
The ProtoNode LEDs indicate functionality as shown
in.
LD29263
DIAGNOSTIC LEDS
FIGURE 61 -
PROTONODE POWER WIRING
TABLE 13 -
DIAGNOSTIC LEDS
TAG
DESCRIPTION
SPL
The SPL LED lights up if the unit is not getting a response from one or more of the configured devices.
For LonWorks units, LED lights up until the unit is commissioned on the LonWorks network.
RUN
The RUN LED starts flashing 20 seconds after the power indicates normal operation.
ERR
The SYS ERR LED lights up 15 seconds after powering up. It turns off after 5 seconds. A steady red light
indicates if there is a system error on the unit. If this occurs, immediately report the related system error shown in
the error screen of the GUI to support for evaluation.
RX
If the socket protocol is serial, the RX LED flashes when the host port receives a message.
If the socket protocol is Ethernet, the RX LED is not used.
TX
If the socket protocol is serial, the TX LED flashes when a message is sent on the host port.
If the socket protocol is Ethernet, the TX LED is not used.
PWR
THE PWR LED is the power light and shows steady green at all times when the unit is powered.
BINDING THE POINTS USING THE .XIF FILE
If you want to bind the points using the
.XIF
file,
complete the following steps the retrieve it from the
ProtoNode:
1. Connect a CAT 5 Ethernet cable (Straight-Thru or
Cross-Over) from the PC to the ProtoNode.
2. Turn off the Wi-Fi on the PC, so it does not try to
connect to a network.
3. Set the PC to a static IP address 192.168.1.11,
Subnet Mask 255.255.255.0.
4. Open the Internet Browser and navigate to the Pro-
toNode address for the .xif file:
192.168.1.24/
fserver.xif
.
5. Save the
.xif
file to the PC.
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...