4. For all OptiView panels (except on YS chillers),
complete the following steps:
1. Connect the power harness from the + PWR
and – PWR terminals on the JCI LON Proto-
Node to the locations as shown in
The power harness, P/N 571-06580-401, is
included in the installation kit.
2. Connect the Frame GND on the ProtoNode
to a ground using the green/yellow wire, P/N
571-06580-403, included in the installation
kit.
3. Trim each of the cables to the required length.
4. Secure the power and communication cables
using wire ties and adhesive mounts provid-
ed in the installation kit.
TABLE 12 -
POWER CONNECTIONS
CHILLER MODEL
PWR+
PWR-
YK OptiView
TB6-162
TB6-5
YZ OptiView
TB7-162
TB7-5
YMC2 OptiView
TB7-162
TB7-5
YD OptiView
TB6-118
TB6-5
YKEP OptiView
TB6-118
TB6-5
YT OptiView
TB1-162
TB6-5
YR OptiView
TB1-162
TB6-5
YST OptiView
TB7-321
TB7-322
For YS OptiView panels, complete the following
steps:
1. Remove the power cable installed between
the micro board and the SC-EQ board.
2. Install the cable, P/N 571-08936-001, as fol-
lows:
• connect P21 to J21 on the micro board
• connect P9 to J9 on the SC-EQ board
• connect the wire end to the ProtoNode
(red wire to PWR+, black wire to PWR-)
3. Trim the cable to the required length at the
ProtoNode end, if needed.
4. Install the Frame GND wire as described
previously in step 4.
LD29259
PWR+
PWR-
GND
FIGURE 57 -
PROTONODE POWER WIRING
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...