USING THE SC-AP FOR TROUBLESHOOTING
The SC-AP is a device that interfaces with Johnson
Controls Connected Chillers service. This device can
also be used to troubleshoot connectivity issues.
If an SC-AP is installed as part of a Connected Servic-
es installation, or if an SC-AP is available otherwise,
connecting it to the SC-EQ allows the technician to
view the port activity to aid in communication prob-
lem diagnosis. It is also required to manually set the
Chiller Model on older YorkTalk2 chillers that do not
auto-discover. Refer to page 34 for instructions on how
to manually set the chiller model. For more detailed
information on the SC-AP refer to
SC-AP Installation
Instructions (Lit 24-10737-75)
and
SC-AP Quick Start
(Lit 24-10737-75)
.
The first screen displayed on the SC-AP after login
is the Device List screen, as shown in
). The example shows two devices, the SC-
AP, and the SC-EQ, as well as their MAC address. The
SC-AP is always MAC address three. In the example
below, the SC-EQ has MAC address four. The Device
List can be used to help troubleshoot issues where the
BAS is not connecting to the SC-EQ.
Selecting the SC-EQ Data tab displays the data for the
SC-EQ. Four of the parameters in the SC-EQ Data tab
display the three communication port settings and the
Online/Offline status of the ports. Refer to
.
The SC-EQ Port Status shows that the Equipment Port
is communicating using YorkTalk 3 and the BAS is
Modbus. The CS port is always BACnet MSTP. If ei-
ther the BAS or the EQ port are not active for a short
period of time, the status is displayed as "Offline." If
the communications is not present for a few minutes,
the status is displayed as "No Protocol." The SC-EQ
continually tries to connect to the absent ports.
FIGURE 46 -
SC-AP DEVICE LIST
LD19990
LD29237
FIGURE 47 -
SC-EQ PORT STATUS AND LOCK IN
SECTION 4 - SC-AP GATEWAY
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...