SECTION 3 - TROUBLESHOOTING
FORM 450.50-N1
ISSUE DATE: 08/19/2019
3
communications are occurring on the BAS bus.
If the voltage reading is steady but out of the
(0.38 VDC to 0.47 VDC) voltage range then the
issue could be improper EOL terminations, issues
with wiring or some other issue. If the BAS trunk
is connected to a third party BAS then the voltage
readings could be acceptable anywhere between
(0.25 VDC to 0.5 VDC).
5. If communications are occurring onthe BAS Bus
then the voltage measured in step 4 should fluc
-
tuate generally in the range of (0.1 VDC to 0.5
VDC) if the bus is properly terminated. The volt-
age readings may vary somewhat out of this range
depending on bus loading and the type of voltme-
ter used. If the voltage readings are fluctuating in
the approximate range of (1.5 VDC to 3.5 VDC)
then it is likely there is no End of Line (EOL) ter-
mination set on the bus and that should be cor-
rected at the EOL device.
LD19997
-
+
SHLD CO
M
BAS Bus
Terminal Block
+
-
V
+
-
V
BAS Bus
Terminal Block
Plug
SH
LD
CO
M
-
+
FIGURE 39 -
BAS BUS METER CHECKS
The meter checks detailed for the BAS
port can also be used for the CS and EQ
ports.
UPDATING THE FIRMWARE AND THE
SOFTWARE
As new chiller data maps become available, it is neces-
sary to update the SC-EQ firmware and software. The
following procedure should be followed to perform a
firmware and software update.
Updating the Firmware
To update the firmware, complete the following steps:
1. Format the USB thumb drive to FAT32.
2. Copy the current
firmware.pkg
from the
CHASE site.
There cannot be other files on the
USB thumb drive.
3. Download the current
firmware.pkg
file. If the
chiller is running, put it in the local mode, so the
SC-EQ does not affect the chiller operation dur-
ing the firmware update.
4. Insert the USB thumb drive into the J3 port on
the SC-EQ board. The firmware update starts au
-
tomatically and the fault LED flashes quickly dur
-
ing the update process.
5. If it does not start automatically, cycle power to
the SC-EQ board by removing and reconnecting
the power plug on the SC-EQ board.
6.
When firmware update is completed, the SC-EQ
reboots. All LEDs go out and then on again. A
typical update takes more than 5 min.
7. When the SC-EQ Fault LED is off for 30 s, the
firmware upgrade is complete. The USB thumb
drive can be removed.
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...