JOHNSON CONTROLS
40
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SECTION 4 - SC-AP GATEWAY
To Change the Device Instance
The SC-EQ automatically creates the Device Instance
as 5000 plus the MAC Address switch setting. For ex-
ample, if the MAC address DIP switches are set to a
value of 6, the Device Instance is 5006. Some custom-
ers require the Device Instance to be something other
than the automatically generated 5000 series address.
The SC-AP can be used to change the Device Instance
to the customer desired address. Connect the SC-AP
to the SC-EQ and log on to the SC-AP using a WiFi
interface either from a Smartphone, a Laptop or Tablet
PC. Refer to
SC-AP Installation (Lit 24-10737-75)
and
SC-AP Quick Start (Lit 24-10737-87
) for more infor-
mation on the SC-AP.
Note that any MAP 4.0 device may be used to connect
to the SC-EQ to change the Device Instance and to also
look at the communication port status. It is not able to
communicate with the Cloud though. When you first
click on a MAP 4.0 device, the Home page loads and
displays a "spinner" that never stops since it is looking
to connect to a Simplicity SE or a RTU controller and
can not find them. The user must just proceed to click
on a menu item on the left-hand side to view informa-
tion.
The MAP1810 device uses two MAC address of 2. So
a temporary change of the SC-EQ mac/node address 2
allows a CS port port mac/node# change as shown in
. The virtual MAC address is separate from
BMS. When it finishes, the address can return to 2.
1. Select the SC-EQ Device then select the SC-EQ
Data tab.
LD29329
FIGURE 48 -
SC-AP DEVICE LIST
A list of parameters is shown on the right side of
your WiFi Smartphone or PC screen.
2. Select the BACNET DEVICE INSTANCE
MODE and change it from AUTO to MANUAL.
Then select SAVE.
FIGURE 49 -
DEVICE INSTANCE MODE
LD29330
3. Next, select the SC-EQUIP BACNET INSTANCE
ID and change it to the desired value. (Must be a
number from 1 to 4914302).
LD19998
E-LINK REPLACEMENT
In BACnet autodiscovery, the E-Link transferred a list
of all possible chiller parameters to the BAS. Even
ones that did not apply. For example, if you had an
Electro-Mechanical starter, the parameters for a VSD
starter were shared by the E-Link and auto-discovered
by the BAS. The SC-EQ discovers what type of chiller
is connected and the chiller features and then exposes
only the relevant points to the BAS. If an E-Link is
replaced by an SC-EQ, the BAS shows the points that
were non relevant previously as Offline. To resolve this
you either need to delete the E-Link and re-discover
the SC-EQ or delete each of the inappropriate Offline
points.
FIGURE 50 -
INVALID POINTS OFFLINE
LD19994
BAS Commands
Points that are commandable show as Unreliable until
the BAS sends the setpoints.
LD19993
FIGURE 51 -
UNRELIABLE REMOTE SETPOINTS
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...