JOHNSON CONTROLS
46
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SECTION 6 - LON PROTONODE
INSTALLATION
The LON ProtoNode can be installed directly into the
chiller control panel of indoor and outdoor chillers.
The ambient operating range is -40°F to 167°F, 5% to
90% RH Non-Condensing. An accessory mounting kit,
P/N 371-06580-000, is used to mount the LON Proto-
Node directly into the chiller control panel.
TABLE 9 -
LON PROTONODE PRODUCT CODE
NUMBERS
DESCRIPTION
PART NUMBER
LON ProtoNode
025-46015-000
OptiView Panel Installation Kit
371-06580-000
Disconnect or isolate all power supplies
before making electrical connections.
More than one disconnect or isolation
may be required to completely de-energize
the equipment. Contact with components
carrying hazardous voltage can cause
electric shock and result in severe per-
sonal injury or death.
Make all wiring connections in accor-
dance with local, national, and regional
regulations. Install the wiring, so it does
not cause a hazard and is protected
against electrical and mechanical dam-
age.
To install the ProtoNode into the chiller control panel,
complete the following steps:
1. All switch and jumper settings must remain at the
factory settings shown in
and
The unit ships with a label covering the externally
accessible switches. This label indicates the set-
tings shown below. No user settings are required
for any of the switches or jumpers and the default
settings are included only for informational pur-
poses.
TABLE 10 -
JUMPER SETTINGS
Bias
OFF
Termination
OFF
A B
Pin 1 and Pin 2
2. Attach the LON ProtoNode to the location shown
in
using the adhesive fasteners, P/N
025-47587-000, included in the installation kit.
LD29257
WASHER
OPTIVIEW
MICROPANEL
FIGURE 55 -
OPTIVIEW LON PROTONODE
MOUNTING LOCATION
3. Connect the LON ProtoNode to the BAS port J12
on the SC-EQ using the communications cable,
P/N 571-06580-402, included in the installation
kit. Connect the wires as shown in
Trim the cable to the required length.
TABLE 11 -
SWITCH SETTINGS
A0
A1
A2
A3
A4
A5
A6
A7
B0
B1
B2
B3
S0
S1
S2
S3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...