JOHNSON CONTROLS
36
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SECTION 3 - TROUBLESHOOTING
Updating the Software
To update the software, complete the following steps:
1. Format the USB thumb drive to FAT32.
2. Copy the current
software.pkg
file on a USB
thumb drive.
There cannot be other files on the
USB thumb drive.
3. Download the current
software.pkg
file. If
the chiller is running, put it in the local mode, so
the SC-EQ does not affect the chiller operation
during the software update.
4. Insert the USB thumb drive into the J3 port on
the SC-EQ board. The software update starts au-
tomatically and the fault LED flashes quickly dur
-
ing the update process.
5. If it does not start automatically, cycle power to
the SC-EQ board by removing and reconnecting
the power plug on the SC-EQ board.
6. When the software update is completed, the SC-
EQ reboots. All LEDs go out and then on again. A
typical update takes more than 5 minutes.
7. When the SC-EQ Fault LED is off for 30 s, the
firmware upgrade is complete. The USB thumb
drive may can removed.
REPAIR INFORMATION
There are no user replaceable parts in the SC-EQ. If the
SC-EQ Comm Card fails to operate within its speci-
fications, replace the unit. For a replacement SC-EQ
Comm Card, contact the nearest Johnson Controls rep-
resentative.
Содержание York Smart Equipment SC-EQ
Страница 4: ...JOHNSON CONTROLS 4 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...JOHNSON CONTROLS 42 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 44: ...JOHNSON CONTROLS 44 FORM 450 50 N1 ISSUE DATE 08 19 2019 THIS PAGE INTENTIONALLY LEFT BLANK...