This group defines supervision for up to three signals from Group 01, Operating Data. Supervision
monitors a specified parameter and energizes a relay output if the parameter passes a defined limit.
Use Group 14, Relay Outputs, to define the relay and whether the relay activates when the signal is too
low or too high.
2QF_#2
23 =,2
! 7
!2,2
4,
#
3201
#%!%!
kk
Q
Selects the first supervised parameter.
• Must be a parameter number from Group 01 Operating Data.
• If the supervised parameter passes a limit, a relay output is energized.
• The supervision limits are defined in this group.
• The relay outputs are defined in Group 14 Relay Outputs (definition also specifies which supervision limit is
monitored).
"&
d
*
Operating data supervision using relay outputs, when
LO
d
HI.
• Case A = Parameter 1401
RELAY OUTPUT
1 (or 1402
RELAY OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
. Use for monitoring when/if the supervised signal
exceeds a given limit. The relay remains active until the
supervised value drops below the low limit.
• Case B = Parameter 1401
RELAY OUTPUT
1 (or 1402
RELAY OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
. Use for monitoring when/if the supervised signal
falls below a given limit. The relay remains active until the
supervised value rises above the high limit.
2,8
Case LO
d
HI represents a normal hysteresis.
"&
!
*
Operating data supervision using relay outputs, when
LO>HI.
The lowest limit (
HI
3203) is active initially, and remains
active until the supervised parameter goes above the
highest limit (
LO
3202), making that limit the active limit.
That limit remains active until the supervised parameter
goes below the lowest limit (
HI
3203), making that limit
active.
• Case A = Parameter 1401
RELAY OUTPUT
1 (or 1402
RELAY OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
. Initially the relay is de-energized. It is energized
whenever the supervised parameter goes above the
active limit.
• Case B = Parameter 1401
RELAY OUTPUT
1 (or 1402
RELAY OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
. Initially the relay is energized. It is de-energized
whenever the supervised parameter goes below the
active limit.
2,8
Case LO>HI represents a special hysteresis with two separate supervision limits.
3202
#%!"*"&
32 =,2
-
60.0 Hz
Sets the low limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
3203
#%!"**
32 =,2
-
60.0 Hz
Sets the high limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
3204
#%!F%!
kk
]
Selects the second supervised parameter. See 3201
SUPERV
1
PARAM
above.
Value of supervised parameter
Case A
0
Energized (1)
0
HI
(3203)
t
t
t
LO
(3202)
Case B
Energized (1)
LO
(3202)
t
HI
(3203)
Value of Supervised Parameter
Case A
0
Energized (1)
0
t
t
Case B
Energized (1)
Active Limit
Содержание York AYK550
Страница 254: ...G YORK A Johnson Controls Company Bypass Package Components Note Solution AHU Does Not have VFD Input Service Switch...
Страница 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Страница 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Страница 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Страница 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Страница 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Страница 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Страница 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Страница 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Страница 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Страница 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Страница 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...