3
YORK, A Johnson Controls Company
$
8112
"&6\!p
>>Z
> Z
Q>#
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
• The first auxiliary motor is running alone.
• AYK550 output frequency drops below the limit:
8112 - 1.
• Output frequency stays below the relaxed limit
(8112 + 1 Hz) for at least the time: 8116
AUX MOT STOP D
.
After the first auxiliary motor stops:
• Output frequency increases by the value =
(8109
START FREQ
1) - (8112
LOW FREQ
1).
• In effect, the output of the speed regulated motor increases to
compensate for the loss of the auxiliary motor.
See figure, where:
• A = (8109
START FREQ
1) - (8112
LOW FREQ
1)
• B = Output frequency decrease during the stop delay.
• C = Diagram showing auxiliary motor’s run status as frequency
decreases (1 = On).
• Grey path = Shows hysteresis – if time is reversed, the path
backwards is not the same. For details on the path for starting,
see the diagram at 8109
START FREQ
1.
Note!
Low Frequency 1 value must be between:
• (2007
MINIMUM FREQ
) +1.
• 8109
START FREQ
1
8113
"&6\!pF
>>Z
> Z
Q>Z#
Sets the frequency limit used to stop the second auxiliary motor.
• See 8112
LOW FREQ
1 for a complete description of the operation.
The second auxiliary motor stops if:
• Two auxiliary motors are running.
• AYK550 output frequency drops below the limit: 8113 - 1.
• Output frequency stays below the relaxed limit (8113 + 1 Hz) for at least the time: 8116
AUX MOT STOP D
.
8114
"&6\!pQ
>>Z
> Z
Q> Z#
Sets the frequency limit used to stop the third auxiliary motor.
• See 8112
LOW FREQ
1 for a complete description of the operation.
The third auxiliary motor stops if:
• Three auxiliary motors are running.
• AYK550 output frequency drops below the limit: 8114 - 1.
• Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116
AUX MOT STOP D
.
8115
m&'#'!'
>Q^>
> X
>
Sets the Start Delay for the auxiliary motors.
• The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
• See 8109
START FREQ
1 for a complete description of the operation.
8116
m&'#'&%>
>Q^>
> X
Q>
Sets the Stop Delay for the auxiliary motors.
• The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time period
before the auxiliary motor stops.
• See 8112
LOW FREQ
1 for a complete description of the operation.
2c_%\
23 =,2
! 7
!2,2
4,
#
t
P 8116
(P 8112)-1
B
f (Hz)
f
MAX
f
MIN
t
1
0
C
P 8112
P 8109
A
A
Содержание York AYK550
Страница 254: ...G YORK A Johnson Controls Company Bypass Package Components Note Solution AHU Does Not have VFD Input Service Switch...
Страница 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Страница 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Страница 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Страница 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Страница 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Страница 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Страница 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Страница 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Страница 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Страница 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Страница 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...