YORK, A Johnson Controls Company
0 =
NOT SEL
.
0.1…1800 = Activates this function using the value entered as the acceleration time.
• A = speed regulated motor accelerating using Group 22 parameters (2202 or 2205).
• B = speed regulated motor decelerating using Group 22 parameters (2203 or 2206).
• At aux. motor start, speed regulated motor decelerates using 8125
DEC IN AUX START
.
• At aux. motor stop, speed regulated motor accelerates using 8124
ACC IN AUX STOP
.
8125
*m#'!'
>c>
>
>
Sets the PFA deceleration time for a maximum-to-zero frequency ramp. This PFA deceleration ramp:
• Applies to the speed regulated motor, when an auxiliary motor is switched on.
• Replaces the deceleration ramp defined in Group 22 ACCEL / DECEL.
• Applies only until the output of the regulated motor decreases by an amount equal to the output of the auxiliary
motor. Then the deceleration ramp defined in Group 22 ACCEL / DECEL applies.
0 =
NOT SEL
.
0.1…1800 = Activates this function using the value entered as the acceleration time.
8126
'*'&
]
Sets the autochange with timer. When enables, autochange is controlled with the timer functions.
0 =
NOT SEL
.
1 = Timer 1 – Enables autochange when Timer 1 is active.
2…4 Timer 2…4 – Enables autochange when Timer 2…4 is active.
8127
'!&\&'
BB]
F
9
Sets the actual number of PFA controlled motors (maximum 6 motors, 1 speed regulated, 3 connected direct-on-line
and 2 spare motors).
• This value includes also the speed regulated motor.
• This value must be compatible with number of relays allocated to PFA if the autochange function is used.
• If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to PFA
but it needs to be included in this value.
8128
m#'!'&!!
Sets the start order of auxiliary motors.
1 = EVEN RUN TIME - The time sharing is active, start order depends on run times.
2 = RELAY ORDER - Start order is fixed to the order of the relays.
2c_%\
23 =,2
! 7
!2,2
4,
#
t
P 8125
P 8124
A
B
1
0
t
f
OUT
Aux.
Motor
Содержание York AYK550
Страница 254: ...G YORK A Johnson Controls Company Bypass Package Components Note Solution AHU Does Not have VFD Input Service Switch...
Страница 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Страница 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Страница 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Страница 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Страница 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Страница 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Страница 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Страница 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Страница 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Страница 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Страница 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...