Selects the source for the timer enable signal.
0 = NOT SEL – Timed functions are disabled.
1 = DI1- Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated for timed functions enable.
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the timed function enable signal.
7 = ENABLED – Timed functions are enabled.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated for timed function enable.
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the timed function enable signal.
3602
#'!''*
__FQ_k_c
F
F__
Defines the daily start time.
• The time can be changed in steps of 2 seconds.
• If parameter value is 07:00:00, then the period will
be activated at 7 a.m.
• The figure shows multiple periods on different
weekdays.
When editing parameters to set times:
• Use arrow keys to select desired hour setting.
• Press NEXT to advance to minutes.
• Use arrow keys to select desired minutes setting.
• Press NEXT to advance to minutes.
• Use arrow keys to select desired seconds setting.
• Press SAVE.
3603
#'&%'*
__FQ_k_c
F
F__
Defines the daily stop time.
• The time can be changed in steps of 2 seconds.
• If the parameter value is 09:00:00, then the period will be deactivated at 9 a.m.
3604
#'!'
g
Defines the weekly start day.
1 = Monday…7 = Sunday.
• If parameter value is 1, then period 1 weekly is active from Monday midnight (00:00:00).
3605
#'&%
g
Defines weekly stop day.
1 = Monday…7 = Sunday.
• If parameter value is 5, then timer 1 weekly will be deactivated on Friday midnight (23:59:58).
3606
#'!''*F
__FQ_k_c
F
F__
Defines timer2 daily start time.
• See parameter 3602
3607
#'&%'*F
__FQ_k_c
F
F__
Defines timer2 daily stop time.
• See parameter 3603
3608
#'!'F
g
Defines timer 2 weekly start day.
• See parameter 3604
00:00:00
09:00:00
10:30:00
12:00:00
13:00:00
15:00:00
17:00:00
20:30:00
Mon Tue Wed Thu
Fri
Sat Sun
Содержание York AYK550
Страница 254: ...G YORK A Johnson Controls Company Bypass Package Components Note Solution AHU Does Not have VFD Input Service Switch...
Страница 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Страница 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Страница 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Страница 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Страница 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Страница 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Страница 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Страница 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Страница 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Страница 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Страница 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...