(8
YORK, A Johnson Controls Company
18
THERM FAIL
Internal fault. The thermistor measuring the internal temperature of the
drive is open or shorted. Contact your local YORK sales representative.
19
OPEX LINK
Internal fault. A communication-related problem has been detected on the
fiber optic link between the OITF and OINT boards. Contact your local
YORK sales representative.
20
OPEX PWR
Internal fault. Low voltage condition detected on OINT power supply.
Contact your local YORK sales representative.
21
CURR MEAS
Internal fault. Current measurement is out of range. Contact your local
YORK sales representative.
22
SUPPLY PHASE
Ripple voltage in the DC link is too high. Check for and correct:
• Missing mains phase.
• Blown fuse.
23
ENCODER ERR
Not used (Available only with encoder and parameter group 50).
24
OVERSPEED
Motor speed is greater than 120% of the larger (in magnitude) of 2001
MINIMUM SPEED
or 2002
MAXIMUM SPEED
. Check for and correct:
• Parameter settings for 2001 and 2002.
• Adequacy of motor braking torque.
• Applicability of torque control.
• Brake chopper and resistor.
25
RESERVED
Not used as of the publication of this manual.
26
DRIVE ID
Internal fault. Configuration Block Drive ID is not valid. Contact your local
YORK sales representative.
27
CONFIG FILE
Internal configuration file has an error. Contact your local YORK sales
representative.
28
SERIAL
1
ERR
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM FAULT FUNC
and 3019
COMM FAULT TIME
).
• Communication settings (Group 51 or 53 as appropriate).
• Poor connections and/or noise on line.
29
EFB CONFIG
FILE
Error in reading the configuration file for the fieldbus adapter.
30
FORCE TRIP
Fault trip forced by the fieldbus. See the fieldbus User’s Manual.
31
EFB
1
Fault code reserved for the EFB protocol application. These codes are not
used as of the publication of this manual.
32
EFB
2
33
EFB
3
34
MOTOR PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
• Motor fault.
• Motor cable fault.
• Thermal relay fault (if used).
• Internal fault.
35
OUTPUT WIRING
Error in power wiring suspected. Check for and correct:
• Input power wired to drive output.
• Ground faults.
36
INCOMP
SWTYPE
The wrong software has been loaded onto the drive. Either standard (ACS)
software has been loaded onto an AYK drive, or HVAC (AYK) software has been
loaded on an ACS drive.
37
CB OVERTEMP
Drive control board is overheated.
Check for and correct:
- Excessive ambient temperature.
- Fan failure.
- Obstructions in the air flow.
\,
23
\,@*
%
=,2 3!=2@@ 332=,=,2
Содержание York AYK550
Страница 254: ...G YORK A Johnson Controls Company Bypass Package Components Note Solution AHU Does Not have VFD Input Service Switch...
Страница 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Страница 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Страница 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Страница 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Страница 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Страница 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Страница 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Страница 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Страница 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Страница 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Страница 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...