Section 2: Installation
Table 2-10 Compatible 2-wire smoke detectors
FSA-210x
FSA-210xR
FSA-210xT
FSA-210xRT
FSA-210xS
FSA-210xRS
FSA-210xST
FSA-210xRST
FSA-210xLST
FSA-210xLRST
Current ratings for DSC FSA-210B series: 35mA - 75mA
Table 2-11 2-wire smoke detector initiating circuit
Item
Specification
Style/Class, Supervised, Power Limited
Style B (Class B)
Compatibility Identifier
PC18-1
DC Output Voltage
9.8-13.8 VDC
Detector Load
2mA (MAX)
Single End-of-Line Resistor (SEOL)
2200
Ω
Loop Resistance
24
Ω
(MAX)
Standby Impedance
1020
Ω
(NOM)
Alarm Impedance
570
Ω
(MAX)
Alarm Current
89mA (MAX)
CO detector
The following hardwired CO detector models can be used with PowerSeries Pro alarm controllers:
l
Potter Model CO-12/24, UL File E321434
l
Quantum Model 12-24SIR, UL File E186246
l
NAPCO Model FW-CO12 or FW-CO1224, UL File E306780
l
System Sensor Model CO1224, UL File E307195
Note:
For multiple unit connections, the leads between CO detectors must be broken. The power supervision relay must be
powered from the last detector in the loop.
Wireless CO detectors are also available. When installing wireless CO detectors, use only model PG9913
UL
, PG8913,
PG4913, or PGx933. An HSM2HOSTx (x=9
UL
/8/4) wireless receiver or HS2LCDRFPRO wireless keypad are required when
installing wireless CO detectors. For more details on these wireless devices, refer to their respective installation manuals.
Note:
Use only
UL
approved devices with UL/ULC listed systems.